Wire size and voltage drop calculator
Enter the load, voltage and distance, and see what wire gauge the circuit needs, the voltage drop, and the breaker size.
Wire size
12 AWG copper
- Needs to carry 20 A; 12 AWG is rated 20 A
- Voltage drop: 2.0% over 30 ft at 120 V
- Breaker: 20 A
A guide only. Electrical work needs a permit in most places, and local code and an electrician have the final word.
Voltage drop by wire size
For your load, voltage and distance. The NEC suggests keeping branch circuits within 3%.
| Wire | Drop | Percent |
|---|---|---|
| 12 AWG recommended Rated 20 A | 2.4 V | 2.0% |
| 10 AWG Rated 30 A | 1.5 V | 1.2% |
| 8 AWG Rated 40 A | 0.9 V | 0.8% |
| 6 AWG Rated 55 A | 0.6 V | 0.5% |
Wire ampacity chart
Maximum amps by wire size, 30°C (86°F) surroundings, up to three current-carrying wires together.
| Wire | Copper NM cable | Copper in conduit | Aluminum | Copper ohms per 1,000 ft |
|---|---|---|---|---|
| 14 AWG | 15 A | 15 A | — | 3.126 |
| 12 AWG | 20 A | 20 A | 15 A | 1.968 |
| 10 AWG | 30 A | 30 A | 25 A | 1.241 |
| 8 AWG | 40 A | 50 A | 40 A | 0.780 |
| 6 AWG | 55 A | 65 A | 50 A | 0.489 |
| 4 AWG | — | 85 A | 65 A | 0.309 |
| 2 AWG | — | 115 A | 90 A | 0.193 |
| 1 AWG | — | 130 A | 100 A | 0.154 |
| 1/0 AWG | — | 150 A | 120 A | 0.122 |
| 2/0 AWG | — | 175 A | 135 A | 0.097 |
| 3/0 AWG | — | 200 A | 155 A | 0.077 |
| 4/0 AWG | — | 230 A | 180 A | 0.061 |
How this works
We take the load in amps (times 125% if it runs three hours or more, as code requires for continuous loads) and find the smallest wire whose rating covers it: the 60°C rating for NM cable, or the 75°C rating for wires in conduit and feeder cable, with the code’s limits of 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper. Then we work out the voltage drop for the round trip, using each wire’s resistance at 75°C, and step up a size until the drop is within 3%.
Be aware: this is a guide for planning and checking a quote. Hot attics, many wires bundled together, motors, and local code amendments can all change the answer, and electrical work usually needs a permit and a licensed electrician. How we estimate.
Related: EV charger installation cost · electrical panel upgrade cost · generator size calculator
Common questions
What size wire do I need for 20 amps?
12 AWG copper for a 20 A circuit, and 14 AWG for 15 A. At a full 20 A load, 12 AWG keeps the voltage drop within 3% up to about 45 ft at 120 V; longer runs need a size up. A 20 A circuit 150 ft away needs 6 AWG.
What size wire for a 48 amp EV charger?
An EV charger counts as a continuous load, so the circuit is sized at 125%: 48 A × 1.25 = 60 A. That means 6 AWG copper wires in conduit on a 60 A breaker, or a bigger wire if the run is long. Many chargers can be set to a lower current to suit an existing circuit.
What is voltage drop and why does it matter?
Wire has resistance, so some voltage is lost along the way, more on long runs and heavy loads. Too much makes motors run hot and lights dim. The National Electrical Code suggests (in an informational note) keeping branch circuits within 3% and the total within 5%. For example, 20 A over 100 ft of 12 AWG drops about 7.9 V, or 6.6% at 120 V.
Copper or aluminum?
Copper carries more current for its size and is used for almost all branch circuits in houses. Aluminum is cheaper and lighter and is common for big feeders, such as the cable to a subpanel or the service, but it needs a larger size for the same current and connectors rated for aluminum.
Why is NM cable rated lower than wire in conduit?
Code limits NM cable (often called Romex) to its 60°C rating, while individual wires in conduit with 75°C terminals can use the higher 75°C rating. That’s why 8 AWG copper NM cable is rated 40 A but 8 AWG wires in conduit are rated 50 A.
Sources and method
- NFPA 70, National Electrical Code . Table 310.16 ampacities, 240.4(D) small-conductor limits, 125% for continuous loads, and the 3% / 5% voltage drop note
- Okonite Cables, Engineering Handbook (2025) . Table 6-25 (NEC 75°C ampacities), Table 1-3 (resistance at 25°C) and Table 1-4 (temperature factors)
Built by Engr. Zakir Ullah, an engineer and Google-certified data analyst. Full method: how we estimate. Last reviewed .